Heat Pump Modular type V-III TROPICAL Series AJY216LNTCH

Outdoor unit

Outdoor Unit :
AJY126LNTCH
Outdoor Unit :
AJY090LNTCH
Download :
Catalogues

Features

  • Excellent energy saving
  • Great design flexibility for placement in any building
  • Easy installation and maintenance
  • Energy-saving technologies for boosting operational efficiency
  • Thorough anti-corrosion treatment
  • Outstanding cooling capacity


Specification

Rated Capacity Range 24 HP
Maximum Connectable Indoor Unit 2 - 40
Indoor unit connectable capacity 34.0 - 88.4 kW
Scroll
Power source Phase 3-phase
Voltage 380-415(50Hz),400(60Hz) V
Frequency 50/60 Hz
Capacity Cooling 68.0 kW
Heating 76.5 kW
Input Power Cooling 18.24 kW
Heating 18.42 kW
EER Cooling 3.73 W/W
COP Heating 4.15 W/W
Air Flow Rate 13000 + 11100 m³/h
Sound Pressure Level*2 Cooling 62 dB(A)
Heating 64 dB(A)
Max. External Static Pressure 82 Pa
Compressor Motor Output 11 x 1 + 7.5 x 1 kW
Heat exchanger fin Blue fin
Net Dimensions
Height X Width X Depth
1690 x 1240 x 765 mm
1690 x 930 x 765 mm
Net Weight 279 kg
255 kg
Refrigerant Type R410A
Charge 11.8 kg
11.7 kg
Connection Pipe Diameter Liquid φ15.88 mm
Gas φ34.92 mm
Max. height difference
(Outdoor Unit: Upper/Lower)
50 / 40 m
Operation Range Cooling -5 to 52 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJY126LNTCH / AJY090LNTCH

Outdoor unit