Heat Recovery Modular Type VR-II Series AJY144GALH  [3Phase]

Outdoor unit

Outdoor Unit :
AJY144GALH
Download :
Catalogue

Features

  • Highly energy-efficient operation
  • Energy-saving technologies for boosting operational efficiency
  • Ideal heat-exchanging path control
  • Sophisticated operation control
  • Flexible piping connection
  • Flexible installation of an RB Unit

Capacity

Cooling  45.0 kW
Heating  50.0 kW

Specification

Rated Capacity Range 16
Maximum Connectable Indoor Unit 24
Indoor unit connectable capacity 22.5 - 67.5 kW
Scroll
Power source Phase 3-phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 45.0 kW
Heating 50.0 kW
Input Power Cooling 13.61 kW
Heating 12.77 kW
EER Cooling 3.31 W/W
COP Heating 3.92 W/W
Air Flow Rate 13,000 m³/h
Sound Pressure Level Cooling 61 dB(A)
Heating 61 dB(A)
Sound Power Level Cooling 82 dB(A)
Heating 83 dB(A)
Max. External Static Pressure 80 Pa
Compressor Motor Output 11.0 kW
Heat exchanger fin Blue fin
Net Dimensions Height 1,690 mm
Width 1,240 mm
Depth 765 mm
Net Weight 286 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8 kg
Connection Pipe Diameter Liquid 12.70 mm
Discharge Gas 22.22 mm
Suction Gas 28.58 mm
Operation Range Cooling -10 to 46 °CDB
Heating -20 to 21 °CDB
Cooling / Heating -10 to 21 °CDB
Scroll
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJY144GALH

Outdoor unit