Heat Recovery Modular Type VR-II Series AJY108GALH  [3Phase]

Outdoor unit

Outdoor Unit :
AJY108GALH
Download :
Catalogue

Features

  • Highly energy-efficient operation
  • Energy-saving technologies for boosting operational efficiency
  • Ideal heat-exchanging path control
  • Sophisticated operation control
  • Flexible piping connection
  • Flexible installation of an RB Unit

Capacity

Cooling  33.5 kW
Heating  37.5 kW

Specification

Rated Capacity Range 12
Maximum Connectable Indoor Unit 17
Indoor unit connectable capacity 16.8 - 50.2 kW
Scroll
Power source Phase 3-phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 33.5 kW
Heating 37.5 kW
Input Power Cooling 9.75 kW
Heating 9.62 kW
EER Cooling 3.44 W/W
COP Heating 3.90 W/W
Air Flow Rate 11,100 m³/h
Sound Pressure Level Cooling 59 dB(A)
Heating 61 dB(A)
Sound Power Level Cooling 80 dB(A)
Heating 83 dB(A)
Max. External Static Pressure 80 Pa
Compressor Motor Output 7.5 kW
Heat exchanger fin Blue fin
Net Dimensions Height 1,690 mm
Width 930 mm
Depth 765 mm
Net Weight 262 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8 kg
Connection Pipe Diameter Liquid 12.70 mm
Discharge Gas 19.05 mm
Suction Gas 28.58 mm
Operation Range Cooling -10 to 46 °CDB
Heating -20 to 21 °CDB
Cooling / Heating -10 to 21 °CDB
Scroll
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJY108GALH

Outdoor unit