Outdoor unit

Outdoor Unit :
AJY144LNLBH
Outdoor Unit :
AJY144LNLBH
Outdoor Unit :
AJY126LNLBH
Download :
Catalogue

Features

  • Excellent energy saving
  • Great design flexibility for placement in any building
  • Easy installation and maintenance
  • Energy-saving technologies for boosting operational efficiency
  • Thorough anti-corrosion treatment
  • Outstanding cooling capacity

Capacity

Cooling  130.0 kW
Heating  145.0 kW

Specification

Rated Capacity Range 46
Maximum Connectable Indoor Unit 55
Indoor unit connectable capacity 65 - 169 kW
Scroll
Power source Phase 3-phase
Voltage ~400 V
Frequency 50,60 Hz
Capacity Cooling 130.0 kW
Heating 145.0 kW
Input Power Cooling 36.98 kW
Heating 38.43 kW
EER Cooling 3.52 W/W
COP Heating 3.77 W/W
Air Flow Rate 13700×2+13000 m³/h
Sound Pressure Level Cooling 66 dB(A)
Heating 68 dB(A)
Sound Power Level Cooling 87 dB(A)
Heating 90 dB(A)
Max. External Static Pressure 82 Pa
Compressor Motor Output 11.0×3 kW
Heat exchanger fin Blue fin
Net Dimensions Height 1690×3 mm
Width 1240×3 mm
Depth 765×3 mm
Net Weight 279×3 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8×3 kg
Connection Pipe Diameter Liquid 19.05 mm
Gas 41.27 mm
Operation Range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJY144LNLBH / AJY144LNLBH / AJY126LNLBH